Counters
CTD (counter down)
Counts down a number setting the output (Q) to True when reaches 0.
Use PV to set the initial value, LOAD to reset the counter and CV to get the current value.
Inputs |
|
CD |
Counts down. |
LOAD |
Resets the counter by loading the preset value. |
PV |
Preset value. |
Outputs |
|
Q |
Q is True when CV is 0, false if otherwise. |
CV |
Current value. |
CTU (counter up)
Counts a number up setting the output (Q) to True when it reaches the preset value (PV).
Use RESET to reset the counter and CV to get the current value.
Inputs |
|
CU |
Counts up. |
RESET |
Resets the counter setting CV to 0. |
PV |
Preset value. |
Outputs |
|
Q |
Q is True when CV is equal to PV, false otherwise. |
CV |
Current value. |
CTUD (counter up/down)
Implements both CTU and CTD counters.
Inputs |
|
CU |
Counts up. |
CD |
Counts down. |
RESET |
Resets the counter, setting CV to 0. |
LOAD |
Loads the counter, setting CV to PV. |
PV |
Preset value. |
Outputs |
|
QU |
QU is True when CV is equal to PV, false otherwise. |
QD |
QD is True when CV is 0, false otherwise. |
CV |
Current value. |